Online UPSs are the most suitable choice, especially for computers and other sensitive devices. These types of UPSs completely isolate your sensitive devices from the network, charge their batteries with electricity from the network, and feed your connected sensitive devices with the help of various filters. As a result, all unwanted situations that may occur in the network are filtered by the online UPS and your sensitive devices are fed with clean energy.
Phase | Single phase and earth |
Rated voltage | 200/208/220/230/240VAC |
Low voltage transfer | 160Vac±5% @100%-80% load; 140Vac±5% @80%-70% load; 120Vac±5% @70%-60% load; 110Vac±5% @60%-0% load; ( <35℃) |
Low voltage correction | 175Vac±5% @100%-80% load; 155Vac±5% @80%-70% load; 135Vac±5% @70%-60% load; 125Vac±5% @60%-0% load; ( <35℃) |
High voltage transfer | 145 or 300Vac ±5% |
High voltage correction | 140 or 290Vac ±5% |
Frequency range | 40-70Hz |
Power factor | 0.990 @100% load (Rated input Voltage) |
Bypass voltage range | Bypass high voltage point can be adjusted from the LCD panel in the range of 230-264 on models with 200/208/220/230/240 VAC output. (Factory value 264Vac); Bypass low voltage point can be adjusted on the LCD panel in the range of 170-220 on models with 200/208/220/230/240 VAC output. (Factory value 170Vac) |
Feeding from generator | Yes |
Output voltage | 200/208/220/230/240Vac |
Power factor | 1 |
Voltage regulation | ±1%(Bat. Mode) |
Frequency | Network Mode47-53Hz or 57-63Hz; Battery Mode (50/60±0.1)Hz |
Crest factor | 3/1 |
Harmonic distortion (THDv) | ≤3% THD linear load; ≤6% THD nonlinear load |
Waveform | Full sine wave |
Transfer time | AC mode <-> Battery mode 0 ms; Inverter <-> bypass 4 ms (Typical) |
Yield | >88%(AC mode); >83%(DC mode) |
Battery Type | 12V7AH |
Battery Type (External Battery) | Depends on the capacity of external batteries |
Number of batteries | 2 |
Number of batteries (External Battery) | 2 |
Support period | Depends on battery capacity |
Typical charging time | 4 hours 90% capacity (Typical) |
Charging voltage | 27.4 VDC ±1% |
Charging voltage (External Battery) | 27.4 VDC ±1% |
Charging current | 1A |
Charging current (External Battery) | 12A |
Overload | Network Mode & Battery Mode, Ambient temperature<35℃ 105%~110% UPS transfers the load to bypass after 10 minutes. 110%~130% UPS transfers the load to bypass after 1 minute. >130% UPS transfers the load to bypass after 3 seconds; 35℃<Ambient temperature.<40℃ 105%~110% UPS transfers the load to bypass after 1 minute. >110% UPS transfers the load to bypass after 3 seconds. / Bypass Mode 8A(Input fuse) |
Short circuit | Output is cut off |
Excessive heat | Transfer to Network Mode Bypass; Battery Mode UPS shuts down |
Low battery voltage | An alarm sounds and the UPS turns off |
Operating temperature | 0℃~40℃ |
Storage temperature | -25℃~55℃ |
Humidity | 20-90% relative humidity @ 0- 40°C (non-condensing) |
Working height | < 1500m |
Noise level | < 50dBA from 1 Meter distance |
DxWxH (mm) | 293x144x209 / 293x144x209 (External Battery Powered Model) |
Weight (kg) | 8.9 / 4.2 (External Battery Powered Model) |
Security | IEC/EN62040-1,IEC/EN60950-1 |
Electro magnetic compatibility | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |