Newtech PRO3 ONE LCD 2 kVA

True double conversion online technology

Online UPSs are the most suitable choice, especially for computers and other sensitive devices. These types of UPSs completely isolate your sensitive devices from the network, charge their batteries with electricity from the network, and feed your connected sensitive devices with the help of various filters. As a result, all unwanted situations that may occur in the network are filtered by the online UPS and your sensitive devices are fed with clean energy.

Multi-function easy-to-read LCD display

Everything is under control with the multifunctional, easy-to-read LCD screen. Thanks to the new advanced LCD screen, functions, input-output values and alarms can be easily monitored.

Introduction
Rated voltage 200 / 208 / 220 / 230 / 240 VAC
Voltage range Low voltage transfer 160 VAC ±5% at 100%-80% load, 140 VAC ±5% at 80%-70% load, 120 VAC ±5% at 70%-60% load, 110 VAC ±5% at 60%-0% load , (<35°C)
Voltage range Low voltage correction 175 VAC ±5% at 100%-80% load, 155 VAC ±5% at 80%-70% load, 135 VAC ±5% at 70%-60% load, 125 VAC ±5% at 60%-0% load , (<35°C)
Voltage range High voltage transfer 300 VAC ± 5%
Voltage range High voltage correction 290 VAC ± 5%
Frequency range 40 Hz ~ 70 Hz
Power factor 0.990 at 100% load (Rated input voltage)
Bypass voltage range Bypass high voltage point on models with 200/208/220/230/240 VAC output
Bypass voltage range Bypass low voltage point on models with 200/208/220/230/240 VAC output
Phase One phase + Earth
Exit
Output voltage 200 / 208 / 220 / 230 / 240 VAC
Output power factor (PF) 1
AC voltage regulation (Battery mode) ±%1
Frequency range (Synchronous mode) 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz
Frequency range (Battery mode) 50 Hz or 60 Hz ± 0.1 Hz
Overload Grid Mode %105-110 by-pass after 10 minutes, 110-130% by-pass after 1 minute, 130-150% by-pass after 3 seconds
Overload Battery Mode %105-110 by-pass after 1 minute, >%110 by-pass after 3 seconds
Current peak ratio (Crest factor) 3/1 max.
Harmonic distortion ≤3% THD (linear load) ≤6% THD (non-linear load)
Transfer time Network <-> Battery mode 0 ms
Transfer time Inverter <-> bypass 4 ms (typical)
Waveform (Battery mode) Full sine wave
Output socket 3 x Schuko
Yield
Network mode ~89%
Battery mode ~87%
Battery
Battery type 12V9AH
Number of batteries 4
Support period Depends on battery capacity
Charging voltage 54.7 VDC ± 1%
Charging current 1A
Indicators & Alarm
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge counter, Error status
Alarm Mains error, Low battery, Overload, System error
Dimensions & Weight
D x W x H (mm) 399 x 144 x 209
Net weight (kg) 16.2
Environmental
Operating temperature 0-40°C
Humidity 20-90% relative humidity (non-condensing)
Noise level < 50 dBA from 1 meter
Software & Management
Smart RS-232 or USB Windows 98/2000/2003/XP/Vista/2008, Windows 7/8, Linux, MAC
SNMP (Optional) Power management with SNMP manager and web browser

    X