Support 24/7
+90 850 201 68 77Send Email
info@tuncmatik.com| Capacity | 250KVA / 200KW |
| Parallel Operation | Up to 4 |
| Rated Voltage | 3 x 360/380/400/415 VAC (3Ph+N) |
| Voltage Range | 110-300 VAC @ 50% load; 176-276 VAC @ 100% load |
| Frequency range | 40~70 Hz |
| Power Factor | > 0.99 at 100% load |
| Harmonic Distortion (THDi) | < 4% linear at full load |
| Output Voltage | 3 x 360*/380*/400/415 VAC (3Ph+N) |
| AC Voltage Regulation (Battery Mode) | ± 1% |
| Frequency Range (Synchronous Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Battery Mode) | 50/60 Hz ± 1% |
| Current Peak Ratio (Crest Factor) | 3/1 (max.) |
| Harmonic Distortion | > 2% THD (Linear Load) |
| Transfer Time | AC mode to battery mode, zero; Inverter to Bypass, zero |
| Output Waveform (Battery Mode) | Full Sine Wave |
| Overload capacity | 100-110% for 10 minutes, 111-130% for 1 minute, >130% for 1s |
| Rated Voltage | 3 x 360/380/400/415 VAC (3Ph+N) |
| Voltage Range | 305VAC~457VAC |
| Frequency range (Synchronous Range) | 46~54Hz or 56~64Hz |
| Overload capacity | > 130% 1 minute (typical) |
| AC Mode | 95.5% |
| ECO Mode | 98.5% |
| Battery Mode | 94.5% |
| Battery (VLRA AGM) | External Battery Group |
| Number of Batteries | 32~40 pieces (Adjustable) |
| Charging Current (max.) | 3-54A, Adjustable |
| Charging Voltage | +/-13.65V*N (N = 16~20) |
| DxWxH (mm) | 974 x 600 x 1600 |
| Net Weight (kg) | 382 |
| Operating Temperature | 0-40°C |
| Ambient Humidity | <95% and non-condensing |
| Height | 0 ~ 1000m at full load |
| Volume | <75 dB @ 1 Meter |
| Smart RS-232/USB | Windows, Linux and MAC support |
| Optional SNMP | Power management via web browser or SNMP manager |
| EPO (Optional) | UPS shuts down immediately |