E-Series 125 kVA 3/3

General Features
Capacity 125KVA / 100KW
Parallel Operation Up to 4
LOGIN
Rated Voltage 3 x 360/380/400/415 VAC (3Ph+N)
Voltage Range 110-300 VAC @ 50% load; 176-276 VAC @ 100% load
Frequency range 40~70 Hz
Power Factor > 0.99 at 100% load
Harmonic Distortion (THDi) < 4% linear at full load
EXIT
Output Voltage 3 x 360*/380*/400/415 VAC (3Ph+N)
AC Voltage Regulation (Battery Mode) ± 1%
Frequency Range (Synchronous Range) 46~54Hz or 56~64Hz
Frequency Range (Battery Mode) 50/60 Hz ± 1%
Current Peak Ratio (Crest Factor) 3/1 (max.)
Harmonic Distortion > 2% THD (Linear Load)
Transfer Time AC mode to battery mode, zero; Inverter to Bypass, zero
Output Waveform (Battery Mode) Full Sine Wave
Overload capacity 100-110% for 10 minutes, 111-130% for 1 minute, >130% for 1s
BYPASS
Rated Voltage 3 x 360/380/400/415 VAC (3Ph+N)
Voltage Range 305VAC~457VAC
Frequency range (Synchronous Range) 46~54Hz or 56~64Hz
Overload capacity > 130% 1 minute (typical)
Yield
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
BATTERY
Battery (VLRA AGM) External Battery Group
Number of Batteries 32~40 pieces (Adjustable)
Charging Current (max.) 2-36A, Adjustable
Charging Voltage +/-13.65V*N (N = 16~20)
DIMENSIONS & WEIGHT
DxWxH (mm) 974 x 600 x 1600
Net Weight (kg) 241
ENVIRONMENTAL
Operating Temperature 0-40°C
Ambient Humidity <95% and non-condensing
Height 0 ~ 1000m at full load
Volume <75 dB @ 1 Meter
SOFTWARE & MANAGEMENT
Smart RS-232/USB Windows, Linux and MAC support
Optional SNMP Power management via web browser or SNMP manager
EPO (Optional) UPS shuts down immediately
Please enable JavaScript in your browser to complete this form.