E-Series 80 kVA 3/3

General Features
Capacity 80KVA / 64KW
Parallel Operation Up to 4
LOGIN
Rated Voltage 3 x 360/380/400/415 VAC (3Ph+N)
Voltage Range 110-300 VAC @ 50% load; 176-276 VAC @ 100% load
Frequency range 40~70 Hz
Power Factor > 0.99 at 100% load
Harmonic Distortion (THDi) < 4% linear at full load
EXIT
Output Voltage 3 x 360*/380*/400/415 VAC (3Ph+N)
AC Voltage Regulation (Battery Mode) ± 1%
Frequency Range (Synchronous Range) 46~54Hz or 56~64Hz
Frequency Range (Battery Mode) 50/60 Hz ± 1%
Current Peak Ratio (Crest Factor) 3/1 (max.)
Harmonic Distortion > 2% THD (Linear Load)
Transfer Time AC mode to battery mode, zero; Inverter to Bypass, zero
Output Waveform (Battery Mode) Full Sine Wave
Overload capacity 100-110% for 10 minutes, 111-130% for 1 minute, >130% for 1s
BYPASS
Rated Voltage 3 x 360/380/400/415 VAC (3Ph+N)
Voltage Range 305VAC~457VAC
Frequency range (Synchronous Range) 46~54Hz or 56~64Hz
Overload capacity > 130% 1 minute (typical)
Yield
AC Mode 95.5%
ECO Mode 98.5%
Battery Mode 94.5%
BATTERY
Battery (VLRA AGM) External Battery Group
Number of Batteries 32~40 pieces (Adjustable)
Charging Current (max.) 1-18A, Adjustable
Charging Voltage +/-13.65V*N (N = 16~20)
DIMENSIONS & WEIGHT
DxWxH (mm) 815 x 300 x 1000
Net Weight (kg) 87
ENVIRONMENTAL
Operating Temperature 0-40°C
Ambient Humidity <95% and non-condensing
Height 0 ~ 1000m at full load
Volume <70 dB @ 1 Meter
SOFTWARE & MANAGEMENT
Smart RS-232/USB Windows, Linux and MAC support
Optional SNMP Power management via web browser or SNMP manager
EPO (Optional) UPS shuts down immediately

    X