X-Long One 5 kVA 1/1

LOGIN
Voltage Range 110-280 VAC
Frequency Range 46 Hz~54 Hz for 50 Hz / 56 Hz~64 Hz for 60 Hz
Phase One phase + Neutral + Earth
Power Factor >0.9 at 100% load
EXIT
Output Voltage 4000W
Output Power Factor (PF) 1
AC Voltage Regulation (Battery Mode) ±5%
Frequency Range (Synchronous) 46 Hz~54 Hz for 50 Hz / 56 Hz~64 Hz for 60 Hz
Frequency Range (Battery Mode) 50 Hz or 60 Hz ±0.1 Hz
Overload (Mains Mode) 105-110% overload alarm, 110-130% by-pass after 30 seconds, 130-150% by-pass after 1.5 seconds
Overload (Battery Mode) 105-110% overload alarm, 110-130% turns off after 30 seconds, 130-150% turns off after 1.5 seconds
Current Peak Ratio (Crest Factor) 3/1 max.
Harmonic Distortion <3% THD (linear load), <6% THD (non-linear load)
Transfer Time Mains - Battery Mode 0 ms; Inverter - Bypass 4 ms (typical)
Waveform (Battery Mode) Full sine wave
Yield
Network Mode ~94%
ECO Mode ~99.5%
Battery Mode ~90%
BATTERY
Battery Voltage 48VDC
Battery Charging Voltage 54.6 VDC
Overload Protection 66 VDC
Charging Current 60A
INDICATOR
LCD Screen UPS status, Load level, Battery level, Input/Output voltage, Discharge counter, Error status
Alarm Battery mode, Low battery, Overload, Error
DIMENSIONS & WEIGHT
D x W x H (mm) 456x190x318
Weight (kg) 15
ENVIRONMENTAL
Operating Temperature 0 - 50°C
Humidity 0-95% relative humidity (non-condensing)
Noise Level <55dBA from 1 meter
SOFTWARE & MANAGEMENT
RJ45 compatibleRS232 input or USB Windows 98/2000/2003/XP/Vista/2008, Windows 7/8, Linux, MAC
SNMP (optional) Power management with SNMP manager and web browser
EPO UPS shuts down immediately