Flexible Scalable Cabinets and Battery System

Modular UPS devices consist of modules that work independently of each other. Modules operate in cabinets produced in various sizes with 5-10-13 slots.

All modules that make up the system are monitored and controlled with the LCD screen positioned on the cabin.

Mechanical manual bypass switch and circuit breaker elements are located in the cabin.

With its unique and special design, MODULTECH UPS does not require access to the side or back of the unit; capacity can be increased by simply adding modules with easy front access.

Why Modular UPS?

The most obvious advantage of modular UPSs is that they can reach greater powers in a smaller area. In critical applications such as datacenters, where each square meter is extremely important and expensive, maximum power should be obtained in the minimum space allocated for UPSs. Modular UPSs meet this requirement. In addition, it provides low energy consumption thanks to its high efficiency and the product pays for itself in a short time.

Maximum Power in Minimum Space
TUNCMATIK brings a new dimension to the field of Uninterruptible Power Supplies with MODULTECH. As a result of its studies, TUNCMATIK has designed MODULTECH, which can respond quickly to the increasing energy demand in accordance with the dynamic structure of today's business world, provides maximum power in minimum space and has a high energy-saving modular structure.
The era of bulky structures occupied by large UPSs ends with MODULTECH. With MODULTECH modular UPS, maximum efficiency is achieved with minimum interruption by occupying less space.
MODULTECH; Data Centers, IT rooms, Telecom, Cable, TV, Banks, Hospitals, Oil and Gas Industry, Universities etc. It will be an indispensable system in places with critical space problems.

Advantages offered by modular structure:

  • Quick installation
  • Quick maintenance without stopping the system
  • Low maintenance cost
  • Low-cost capacity expansion
  • N+Y redundant operation possibility
  • Plug and play power modules
  • Flexible scalable UPS cabinet
  • Flexible scalable battery cabinets

Grows with your business.

The most suitable architecture for capacity increases that may arise in the future.
For example; For a data center with a requirement of 240kVA, 240kVA can be obtained by using 8 pieces of 30kVA modules with a 10-module capacity cabinet. There are two empty module slots in the cabinet. As the data center load decreases, 30kVA modules can be added to the cabinet and the power can be increased up to 300kVA without any additional investment.

Discover Features

External Battery Connection

You can extend the support time of the product by connecting an external battery.

High Input Power Factor

It does not impose additional compensation load on your network. It saves money on your electricity bills.

Smart Charging Technology

Since it charges the battery with a special charging technique, it extends battery life, reduces your operating costs and saves money.

High Output Power Factor

It provides 28% more power at its output compared to standard 0.7 power factor UPSs. Supports more electrical/electronic devices.

High Performance Microprocessor

Thanks to its digital structure and high speed, the CPU-controlled control card provides full protection by performing protection functions of the UPS such as overload, short circuit, low-high voltage and overheat in a timely manner, thus ensuring that the UPS has a stable and reliable structure.

True Sine Wave Output

Full compatibility with all types of electrical devices, the ideal solution for your medical and similar critical applications.

High Energy Saving

Thanks to Eco mode, the load is fed from your network. When the mains voltage goes out of limits or is cut off, UPS comes into play and feeds the load.

Cold Start

It has the ability to be operated directly from batteries in cases where there is no mains electricity.

High Online Yield

Thanks to high online efficiency, it saves energy and reduces your energy costs.

Introduction
Rated voltage 380/400/415 VAC, (3 phase+neutral+ground)
Voltage range 208-478 VAC
Frequency range 40 - 70 Hz
Power factor ≥ 0.99
Bypass voltage range Max. voltage. 220V +25% (optional +10%, +15%,+20%) 230V 20% (optional +10%, +15%) 240V 15% (optional +10%) Min. voltage -45% (optional -20%, -30%) Frequency protection range. ±10%
Harmonic distortion (THDi) 2% (100% non-linear load)
Generator input Supports
Exit
Output voltage 380/400/415 VAC, (3 phase+neutral+ground)
Voltage regulation ±%1
Power factor 0.9/1
Output frequency 1. Network mode
Current peak ratio (Crest factor) 3/1
Harmonic distortion (THDi) ≤ 2% (linear load) / ≤ 5% (non-linear load)
Yield 95.5%
Battery
Battery voltage ±240VDC; number of batteries (optional)
Charging current UPS cabinet 100A (Max.)
Charging current Module 10A (Max.) (charging current can be adjusted according to battery capacity)
Backup time depends on external battery capacity
System Features
Transfer time Grid to battery
Overload Grid mode Load ≤110%
Overload Battery mode Load ≤110%
Overload Bypass mode Breaker (30kVA
Short circuit Available
Noise reduction EN62040-2 compliant
Communication interface UPS cabinet
Environmental
Operating temperature 0 ~ 40°C
Storage temperature -25 ~ 55°C
Humidity 0 ~ 95% (non-condensing)
Working height < 1500m
Noise level < 65dB
Dimensions & Weight
Dimensions D x W x H (mm) UPS cabinet 600 x 1100 x 2000
Dimensions D x W x H (mm) Module 443 x 580 x 131 (3U)
Net weight (kg) UPS cabinet 310
Net weight (kg) Module 33
* Optional 10,15, 20 kVA available
** Diffrent Cabinets sizes available
Indicators & Alarm
LCD panel UPS status, Load level, Battery level, Input/Output voltage, Discharge time, Error status
Alarm Battery mode, Low battery, Overload, Error
Standard Certificates
Security IEC/EN62040-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8