Support 24/7
+90 850 201 68 77Send Email
info@tuncmatik.comFlexible Scalable Cabinets and Battery System
Modular UPS devices consist of modules that work independently of each other. Modules operate in cabinets produced in various sizes with 5-10-13 slots.
All modules that make up the system are monitored and controlled with the LCD screen positioned on the cabin.
Mechanical manual bypass switch and circuit breaker elements are located in the cabin.
With its unique and special design, MODULTECH UPS does not require access to the side or back of the unit; capacity can be increased by simply adding modules with easy front access.
The most obvious advantage of modular UPSs is that they can reach greater powers in a smaller area. In critical applications such as datacenters, where each square meter is extremely important and expensive, maximum power should be obtained in the minimum space allocated for UPSs. Modular UPSs meet this requirement. In addition, it provides low energy consumption thanks to its high efficiency and the product pays for itself in a short time.
The most suitable architecture for capacity increases that may arise in the future.
For example; For a data center with a requirement of 240kVA, 240kVA can be obtained by using 8 pieces of 30kVA modules with a 10-module capacity cabinet. There are two empty module slots in the cabinet. As the data center load decreases, 30kVA modules can be added to the cabinet and the power can be increased up to 300kVA without any additional investment.
You can extend the support time of the product by connecting an external battery.
It does not impose additional compensation load on your network. It saves money on your electricity bills.
Since it charges the battery with a special charging technique, it extends battery life, reduces your operating costs and saves money.
It provides 28% more power at its output compared to standard 0.7 power factor UPSs. Supports more electrical/electronic devices.
Thanks to its digital structure and high speed, the CPU-controlled control card provides full protection by performing protection functions of the UPS such as overload, short circuit, low-high voltage and overheat in a timely manner, thus ensuring that the UPS has a stable and reliable structure.
Full compatibility with all types of electrical devices, the ideal solution for your medical and similar critical applications.
Thanks to Eco mode, the load is fed from your network. When the mains voltage goes out of limits or is cut off, UPS comes into play and feeds the load.
It has the ability to be operated directly from batteries in cases where there is no mains electricity.
Thanks to high online efficiency, it saves energy and reduces your energy costs.
Rated voltage | 380/400/415 VAC, (3 phase+neutral+ground) |
Voltage range | 208-478 VAC |
Frequency range | 40 - 70 Hz |
Power factor | ≥ 0.99 |
Bypass voltage range | Max. voltage. 220V +25% (optional +10%, +15%,+20%) 230V 20% (optional +10%, +15%) 240V 15% (optional +10%) Min. voltage -45% (optional -20%, -30%) Frequency protection range. ±10% |
Harmonic distortion (THDi) | 2% (100% non-linear load) |
Generator input | Supports |
Output voltage | 380/400/415 VAC, (3 phase+neutral+ground) |
Voltage regulation | ±%1 |
Power factor | 0.9/1 |
Output frequency | 1. Network mode |
Current peak ratio (Crest factor) | 3/1 |
Harmonic distortion (THDi) | ≤ 2% (linear load) / ≤ 5% (non-linear load) |
Yield | 95.5% |
Battery voltage | ±240VDC; number of batteries (optional) |
Charging current UPS cabinet | 100A (Max.) |
Charging current Module | 10A (Max.) (charging current can be adjusted according to battery capacity) |
Backup time depends on external battery capacity |
Transfer time | Grid to battery |
Overload Grid mode | Load ≤110% |
Overload Battery mode | Load ≤110% |
Overload Bypass mode | Breaker (30kVA |
Short circuit | Available |
Noise reduction | EN62040-2 compliant |
Communication interface | UPS cabinet |
Operating temperature | 0 ~ 40°C |
Storage temperature | -25 ~ 55°C |
Humidity | 0 ~ 95% (non-condensing) |
Working height | < 1500m |
Noise level | < 65dB |
Dimensions D x W x H (mm) UPS cabinet | 600 x 1100 x 2000 |
Dimensions D x W x H (mm) Module | 443 x 580 x 131 (3U) |
Net weight (kg) UPS cabinet | 310 |
Net weight (kg) Module | 33 |
* Optional 10,15, 20 kVA available | |
** Diffrent Cabinets sizes available |
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge time, Error status |
Alarm | Battery mode, Low battery, Overload, Error |
Security | IEC/EN62040-1, IEC/EN60950-1 |
EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |