Online UPSs are the most suitable choice, especially for computers and other sensitive devices. These types of UPSs completely isolate your sensitive devices from the network, charge their batteries with electricity from the network, and feed your connected sensitive devices with the help of various filters. As a result, all unwanted situations that may occur in the network are filtered by the online UPS and your sensitive devices are fed with clean energy.
Phase | One phase + Neutral + Earth |
Rated Voltage | 220/230/240 Vac |
Voltage Range | 120~276 Vac |
Frequency Range | 50 Hz at 45-55 Hz / 60 Hz at 54-66 Hz (automatic selection) |
Current (THDi) | ≤3% (linear load); ≤5% (non-linear load) |
Bypass Voltage Range | 220Vac max. voltage +25% (optional +10%, +15%, +20%); 230Vac max. voltage +20% (optional +10%, +15%); 240Vac max. voltage +15% (optional +10%); Min voltage -45% (optional -20%, -30%); Bypass frequency range +1%, +2%, +4%, +5%, +10% |
Power Factor | >0.99 (input THDv ≤%1) |
Phase | One phase + Neutral + Earth |
Rated Voltage | 220/230/240 Vac |
Power Factor | 0.9 |
Voltage Regulation | ±1.0% |
Frequency | Normal mode, same as mains frequency / Battery mode, (50/60 ±0.1%) Hz |
Crest Factor | 3/1 |
THD | ≤2% (linear load); ≤5% (non-linear load) |
Efficiency <92% |
Type & Quantity | 12V9AHx16 |
Charging Current (A) | 1.0A |
Transfer Time | Mains - Battery 0 ms, Mains - Bypass 0 ms |
Overload (AC Mode) | 60min at 105%~110% load; 10min at 110%~125% load; 1min at 125%~150% load; >200ms at 150% load |
Overload (Battery Mode) | 10min at 105%~110% load; 1min at 110%~125% load; >200ms at 125% load |
Overload (Bypass Mode) | 63A Fuse |
Over Temperature | Alarm |
Battery Low | Alarm and shut down |
Test | With software |
EPO | UPS shuts down immediately |
Battery | Smart battery management |
DxWxH (mm) | 460x191x720 |
Weight (kg) | 121 |
Status LED & LCD | Mains mode, Bypass mode, Battery low, Battery faulty, Overload, Fault |
LCD Panel | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage and temperature |
Voice & Display | Mains error, Battery low, Overload, System error |
Operating Temperature | 0°C~40°C |
Humidity | 0~95% non-condensing |
Height | <1500m |
Noise Level | <55dB from 1 meter |
Interfaces | USB, RS232, SNMP Card (optional) |
EMC | IEC62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5 |
Security | IEC62040-1, GB4943-2005 |