PowerUP ONE 10 kVA

True double conversion online technology

Online UPSs are the most suitable choice, especially for computers and other sensitive devices. These types of UPSs completely isolate your sensitive devices from the network, charge their batteries with electricity from the network, and feed your connected sensitive devices with the help of various filters. As a result, all unwanted situations that may occur in the network are filtered by the online UPS and your sensitive devices are fed with clean energy.

LOGIN
Phase One phase + Neutral + Earth
Rated Voltage 220/230/240 Vac
Voltage Range 120~276 Vac
Frequency Range 50 Hz at 45-55 Hz / 60 Hz at 54-66 Hz (automatic selection)
Current (THDi) ≤3% (linear load); ≤5% (non-linear load)
Bypass Voltage Range 220Vac max. voltage +25% (optional +10%, +15%, +20%); 230Vac max. voltage +20% (optional +10%, +15%); 240Vac max. voltage +15% (optional +10%); Min voltage -45% (optional -20%, -30%); Bypass frequency range +1%, +2%, +4%, +5%, +10%
Power Factor >0.99 (input THDv ≤%1)
EXIT
Phase One phase + Neutral + Earth
Rated Voltage 220/230/240 Vac
Power Factor 0.9
Voltage Regulation ±1.0%
Frequency Normal mode, same as mains frequency / Battery mode, (50/60 ±0.1%) Hz
Crest Factor 3/1
THD ≤2% (linear load); ≤5% (non-linear load)
Efficiency <92%
BATTERY
Type & Quantity 12V9AHx16
Charging Current (A) 1.0A
Transfer Time Mains - Battery 0 ms, Mains - Bypass 0 ms
PROTECTION
Overload (AC Mode) 60min at 105%~110% load; 10min at 110%~125% load; 1min at 125%~150% load; >200ms at 150% load
Overload (Battery Mode) 10min at 105%~110% load; 1min at 110%~125% load; >200ms at 125% load
Overload (Bypass Mode) 63A Fuse
Over Temperature Alarm
Battery Low Alarm and shut down
Test With software
EPO UPS shuts down immediately
Battery Smart battery management
DIMENSIONS & WEIGHT
DxWxH (mm) 460x191x720
Weight (kg) 121
INDICATORS & ALARM
Status LED & LCD Mains mode, Bypass mode, Battery low, Battery faulty, Overload, Fault
LCD Panel Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage and temperature
Voice & Display Mains error, Battery low, Overload, System error
ENVIRONMENTAL
Operating Temperature 0°C~40°C
Humidity 0~95% non-condensing
Height <1500m
Noise Level <55dB from 1 meter
SOFTWARE & MANAGEMENT
Interfaces USB, RS232, SNMP Card (optional)
STANDARD
EMC IEC62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5
Security IEC62040-1, GB4943-2005