Support 24/7
+90 850 201 68 77Send Email
info@tuncmatik.comTrue double conversion online technology
Online UPSs are the most suitable choice, especially for computers and other sensitive devices. These types of UPSs completely isolate your sensitive devices from the network, charge their batteries with electricity from the network, and feed your connected sensitive devices with the help of various filters. As a result, all unwanted situations that may occur in the network are filtered by the online UPS and your sensitive devices are fed with clean energy.
True sine wave output
Full compatibility with all types of electrical devices, the ideal solution for your medical and similar critical applications.
You can extend the support time of the product by connecting an external battery.
Ability to work online even at very low and very high voltages without switching to battery.
Since it charges the battery with a special charging technique, it extends battery life, reduces your operating costs and saves money.
It does not impose additional compensation load on your network. It saves money on your electricity bills.
Thanks to its digital structure and high speed, the CPU-controlled control card provides full protection by performing protection functions of the UPS such as overload, short circuit, low-high voltage and overheat in a timely manner, thus ensuring that the UPS has a stable and reliable structure.
It provides 15% more power at its output compared to standard 0.7 power factor UPSs. Supports more electrical/electronic devices.
15% more power at output compared to standard 0.7 power factor UPS systems. It can support more equipment.
Full compatibility with all types of electrical devices, the ideal solution for your medical and similar critical applications.
It has the ability to be operated directly from batteries in cases where there is no mains electricity.
Thanks to high online efficiency, it saves energy and reduces your energy costs.
Voltage range Low voltage transfer | 110 VAC ± 3% at 50% load, 176 VAC ± 3% at 100% load |
Voltage range Low voltage correction | 120 VAC ± 3% at 50% load, 186 VAC ± 3% at 100% load |
Voltage range High voltage transfer | 300 VAC (L-N) ± 3% |
Voltage range High voltage correction | 290 VAC ± 3% |
Frequency range | 46 Hz ~ 54 Hz for 50 Hz system, 56 Hz ~ 64 Hz for 60 Hz system |
Power factor | ≥ 0.99 (at 100% load) |
Phase | Three phase + Neutral + Earth |
Phase | One phase + Neutral + Earth |
Output voltage | 208 / 220 / 230 / 240 VAC |
Output power factor | (PF) |
AC voltage regulation (Battery mode) | ±%1 |
Frequency range (Synchronous mode) | 46 Hz ~ 54 Hz for 50 Hz system; 56 Hz ~ 64 Hz for 60 Hz system |
Frequency range (Battery mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Overload Mains mode | 100% ~ 110% |
Battery Overload mode | 100% ~ 110% |
Current peak ratio (Crest factor) | 3/1 max |
Harmonic distortion | ≤ 2% THD (linear load), ≤ 5% THD (non-linear load) |
Transfer Time Mains ↔ Battery | 0 ms |
Transfer Time Inverter ↔ By-pass | 0 ms |
Transfer Time Inverter ↔ ECO | <10 ms |
Network mode | ~ 91.5% |
Battery mode | ~87% |
Standard model Type & quantity | 12V 9Ah x 20 |
Standard model Charging time | 9 hours up to 90% capacity |
Standard model Charging current | 1.0 A ± 10% max. |
Standard model Charging voltage | 273 VDC ± 1% |
Long term model Type & quantity | Type |
Long-term model Charging time | Depends on external battery capacity |
Long-term model Charging current | 4.0 A ± 10% max. |
Long-term model Charging voltage | 286 VDC ± 1% |
LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge counter, Error status |
Alarm | Battery mode, Low battery, Overload, Error |
Standard Model D x W x H (mm) | 592 x 250 x 576 |
Standard Model Net weight (kg) | 83 |
Long Model D x W x H (mm) | 592 x 250 x 576 |
Long Model Net weight (kg) | 26 |
Operating temperature | 0 ~ 40°C (Battery life decreases at temperatures higher than 25°C) |
Humidity | 20-95% relative humidity (non-condensing) |
Working height | < 1000 m |
Noise level | < 58 dBA from 1 meter |